Linear Sensitivity Factors
|
|
==========================
|
|
|
|
UnitCommitment.jl includes a number of functions to compute typical linear sensitivity
|
|
factors, such as [Injection Shift Factors](@ref) and [Line Outage Distribution Factors](@ref). These sensitivity factors can be used to quickly compute DC power flows in both base and N-1 contigency scenarios.
|
|
|
|
Injection Shift Factors
|
|
-----------------------
|
|
Given a network with `B` buses and `L` transmission lines, the Injection Shift Factors (ISF) matrix is an `L`-by-`B` matrix which indicates much power flows through a certain transmission line when 1 MW of power is injected at bus `b` and withdrawn from the slack bus. For example, `isf[:l7, :b5]` indicates the amount of power (in MW) that flows through line `l7` when 1 MW of power is injected at bus `b5` and withdrawn from the slack bus.
|
|
This matrix is computed based on the DC linearization of power flow equations and does not include losses.
|
|
To compute the ISF matrix, the function `injection_shift_factors` can be used. It is necessary to specify the set of lines, buses and the slack bus:
|
|
```julia
|
|
using UnitCommitment
|
|
instance = UnitCommitment.load("ieee_rts/case14")
|
|
isf = UnitCommitment.injection_shift_factors(lines = instance.lines,
|
|
buses = instance.buses,
|
|
slack = :b14)
|
|
@show isf[:l7, :b5]
|
|
``` |